電信設備接地的注意事項

发布:2019年07月25日编号:2056-471801
小生活网提醒您:1、在办理服务前请确认对方资质, 夸大的宣传和承诺不要轻信!2.任何要求预付定金、汇款至个人银行账户等方式均存在风险,谨防上当受骗!
详细描述

為防止外界電壓危害人身安全和對設備的損害,抑制電氣干擾,保證通信設備正常工作来源www.xbaixing.com

電信設備接地的注意事項

1.當低壓配電系統採取tn制式供電,電信設備若要求嚴格限制工頻交流對其的干擾

2.若電信設備不易做到與站內各種金黃色屬構件絕緣時,應採用tn-s制式;

3.當對干擾要求不太嚴格時,可採用tn-c制式;

4.當電信設備的泄漏電流在10ma及以上時,應採用tn-s制式;

5.當採取it制式供電,電信設備的泄漏電流在10ma以上時,為了避免保護設備誤動作,可採取雙線圈變壓器供電fry

6.電信設備的工作接地,一般要求單獨設置,與建築物內變壓器的工作接地共用一個接地裝置時,必須通過絕緣的專用接地線與接地裝置相連;

7.電信設備採用共同接地裝置時,其接地電阻應不大於1ω,用兩根截面積不小於25mm2的銅芯絕緣線穿管敷設到共同接地極上x~b~a~i~x~i~n~g~c~o~m。當採用基礎鋼筋作為共同接極時,連接處應有銅鐵過渡接頭来自www.xbaixing.com

* * * * * *

創世服務有限公司是一間提供專業數據中心架設公司,擁有一群專業團隊貼心地關注客戶的要求,並提供優質的服務x.b.a.i.x.i.n.g.c.o.m

想了解更多關於「電信設備接地的注意事項」的內容,請瀏覽創世官網:http://livservices.com.hk

地址: 香港觀塘鴻圖道37-39號鴻泰工業大廈4樓4室

電話:852-31063235

——————

Precautions for grounding of telecommunication equipment

1. When the low-voltage power distribution system adopts the tn system power supply, if the telecommunication equipment requires strict restriction on the interference of the power frequency communication

2. If the telecommunication equipment is not easy to be insulated from the various golden components in the station, the tn-s system should be adopted;

3. When the interference requirements are not strict, the tn-c system can be adopted;

4. When the leakage current of telecommunication equipment is 10ma or more, the tn-s system should be adopted;

5. When the power supply of the standard system is used, when the leakage current of the telecommunication equipment is above 10ma, in order to avoid the malfunction of the protection device, the power supply of the double coil transformer can be adopted.

6. The working grounding of telecommunication equipment is generally required to be set separately. When sharing a grounding device with the working ground of the transformer in the building, it must be connected to the grounding device through a dedicated grounding wire for insulation;

7. When the telecommunication equipment adopts the common grounding device, its grounding resistance should be no more than 1ω, and it should be laid on the common grounding pole with two copper insulated wires with a cross-sectional area of not less than 25mm2. When the base steel bars are used as common joints, there should be copper-iron transition joints at the joints.

* * * * * *

LIV is a professional data center to set up a company, with a group of professional team intimate attention to customer requirements, and provide quality services.

For more information about 'Precautions for grounding of telecommunication equipment',please visit : http://livservices.com.hk

Address: Unit 4, 4/F., Hung Tai Industrial Building,37-39 Hung To Road, Kwun Tong, Hong Kong

Tel: +852 3106 3235


展开更多描述 ↓
dxstybud 注册时间:2019年07月08日
该用户还发布了
精选信息
热门信息
在线留言 发送短信 拨打电话